Surge arresters may represent an efficient choice for limiting lightning surge effects, significantly reducing the outage rate of power lines. The present work firstly presents an efficient numerical approach suitable for insulation coordination studies based on an implicit Crank-Nicolson finite difference time domain method; then, the IEEE recommended surge arrester model is reviewed and implemented by means of a local implicit scheme, based on a set of non-linear equations, that are recast in a suitable form for efficient solution. The model is proven to ensure robustness and second-order accuracy. The implementation of the arrester model in the implicit Crank-Nicolson scheme represents the added value brought by the present study. Indeed, its preserved stability for larger time steps allows reducing running time by more than 60% compared to the well-known finite difference time domain method based on the explicit leap-frog scheme. The reduced computation time allows faster repeated solutions, which need to be looked for on assessing the lightning performance (randomly changing, parameters such as peak current, rise time, tail time, location of the vertical leader channel, phase conductor voltages, footing resistance, insulator strength, etc. would need to be changed thousands of times).

Analysis of metal oxide varistor arresters for protection of multiconductor transmission lines using unconditionally-stable Crank-Nicolson FDTD / Stracqualursi, E.; Araneo, R.; Lovat, G.; Andreotti, A.; Burghignoli, P.; Faria, J. B.; Celozzi, S.. - In: ENERGIES. - ISSN 1996-1073. - 13:8(2020), pp. 1-19. [10.3390/en13082112]

Analysis of metal oxide varistor arresters for protection of multiconductor transmission lines using unconditionally-stable Crank-Nicolson FDTD

Stracqualursi E.;Araneo R.;Lovat G.;Burghignoli P.;Celozzi S.
2020

Abstract

Surge arresters may represent an efficient choice for limiting lightning surge effects, significantly reducing the outage rate of power lines. The present work firstly presents an efficient numerical approach suitable for insulation coordination studies based on an implicit Crank-Nicolson finite difference time domain method; then, the IEEE recommended surge arrester model is reviewed and implemented by means of a local implicit scheme, based on a set of non-linear equations, that are recast in a suitable form for efficient solution. The model is proven to ensure robustness and second-order accuracy. The implementation of the arrester model in the implicit Crank-Nicolson scheme represents the added value brought by the present study. Indeed, its preserved stability for larger time steps allows reducing running time by more than 60% compared to the well-known finite difference time domain method based on the explicit leap-frog scheme. The reduced computation time allows faster repeated solutions, which need to be looked for on assessing the lightning performance (randomly changing, parameters such as peak current, rise time, tail time, location of the vertical leader channel, phase conductor voltages, footing resistance, insulator strength, etc. would need to be changed thousands of times).
2020
FDTD; metal oxide varistors arresters; protection; transmission lines
01 Pubblicazione su rivista::01a Articolo in rivista
Analysis of metal oxide varistor arresters for protection of multiconductor transmission lines using unconditionally-stable Crank-Nicolson FDTD / Stracqualursi, E.; Araneo, R.; Lovat, G.; Andreotti, A.; Burghignoli, P.; Faria, J. B.; Celozzi, S.. - In: ENERGIES. - ISSN 1996-1073. - 13:8(2020), pp. 1-19. [10.3390/en13082112]
File allegati a questo prodotto
File Dimensione Formato  
Stracqualursi_Analysis_2020.pdf

accesso aperto

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Creative commons
Dimensione 1.59 MB
Formato Adobe PDF