Large-scale ground-mounted PV plants, because of their large extend and localization, can be subject to lightning strikes. When a lightning strike falls into the area of the PV plant, the earthing system is affected by the current flowing in the lightning channel and potentially dangerous overvoltages may occur. Thus, the investigation on the performance of the grounding system is of paramount interest for the prediction of the potential threats either for people working in (or animals passing through) the solar farm area and for the installed electric and electronic equipments. The analysis of grounding systems is conducted in the frequency domain and an hybrid approach, based on circuit theory and Method of Moments, is adopted in order to fully account for resistive, inductive and capacitive couplings between elements of the ground system. The actual transient behavior is obtained by means of an Inverse Fourier Transform. A real case study grounding system configuration is considered and analyzed. We show that, even if the requirements of the international standards are fulfilled, and touch and step voltages are controlled with special care, overvoltages may cause failures of internal systems.

Analysis of the lightning transient response of the earthing system of large-scale ground-mounted PV plants / Araneo, Rodolfo; Maccioni, Marco; Lauria, Stefano; Celozzi, Salvatore. - (2017), pp. 1-6. (Intervento presentato al convegno 2017 IEEE Manchester PowerTech, Powertech 2017 tenutosi a Manchester, ENGLAND nel 2017) [10.1109/PTC.2017.7981087].

Analysis of the lightning transient response of the earthing system of large-scale ground-mounted PV plants

Araneo, Rodolfo;Maccioni, Marco
;
Lauria, Stefano;Celozzi, Salvatore
2017

Abstract

Large-scale ground-mounted PV plants, because of their large extend and localization, can be subject to lightning strikes. When a lightning strike falls into the area of the PV plant, the earthing system is affected by the current flowing in the lightning channel and potentially dangerous overvoltages may occur. Thus, the investigation on the performance of the grounding system is of paramount interest for the prediction of the potential threats either for people working in (or animals passing through) the solar farm area and for the installed electric and electronic equipments. The analysis of grounding systems is conducted in the frequency domain and an hybrid approach, based on circuit theory and Method of Moments, is adopted in order to fully account for resistive, inductive and capacitive couplings between elements of the ground system. The actual transient behavior is obtained by means of an Inverse Fourier Transform. A real case study grounding system configuration is considered and analyzed. We show that, even if the requirements of the international standards are fulfilled, and touch and step voltages are controlled with special care, overvoltages may cause failures of internal systems.
2017
2017 IEEE Manchester PowerTech, Powertech 2017
circuit theory; grounding systems; lightning; method of moments; multilayered earth; PV plants; control and optimization; modeling and simulation; computer networks and communications; energy engineering and power technology
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
Analysis of the lightning transient response of the earthing system of large-scale ground-mounted PV plants / Araneo, Rodolfo; Maccioni, Marco; Lauria, Stefano; Celozzi, Salvatore. - (2017), pp. 1-6. (Intervento presentato al convegno 2017 IEEE Manchester PowerTech, Powertech 2017 tenutosi a Manchester, ENGLAND nel 2017) [10.1109/PTC.2017.7981087].
File allegati a questo prodotto
File Dimensione Formato  
Araneo_Analysis_2017.pdf

solo gestori archivio

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 274.38 kB
Formato Adobe PDF
274.38 kB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/1091510
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 14
  • ???jsp.display-item.citation.isi??? 4
social impact