This paper documents the causes of the scaling of stripping towers used for the treatment of groundwater polluted by the leachate from an old municipal solid waste (MSW) landfill in northern Italy. The effects of the scaling on the stripping performance are also reported. The whole process consists of a coagulation-flocculation pre-treatment at pH > 11, followed by an ammonia stripping stage, after heating the water to 38°C in order to improve removal efficiency. The stripped ammonia is recovered by absorption with sulfuric acid, producing a 30% solution of ammonium sulfate (reused as a base fertilizer). The effluent air stream is recirculated to the stripping towers (closed loop systems) in order to avoid an excessive temperature drop inside the packings, mainly in winter, with consequent loss of efficiency and risk of icing. The progressive scaling of the packing has resulted in a loss of ammonia removal efficiency from an initial value of 98% (clean packing) down to 80% after six months of continuous operation, necessitating a chemical cleaning. Optimum conditions for design and operation of the stripping process are also documented. © 2015, Institute for Environmental Research in Hydrographic Basins (IPABHi). All rights reserved.
Scaling of ammonia stripping towers in the treatment of groundwater polluted by municipal solid waste landfill leachate. Study of the causes of scaling and its effects on stripping performance / Incrustação das torres de arraste de amônia no tratamento de águas subterrâneas poluídas pelo chorume de aterro de resíduos sólidos urbanos. Estudo das causas da incrustação e seus efeitos na eficiência de extração / Viotti, Paolo; Gavasci, Renato. - In: REVISTA AMBIENTE & ÁGUA. - ISSN 1980-993X. - ELETTRONICO. - 10:2(2015), pp. 240-252. [10.4136/ambi-agua.1567]
Scaling of ammonia stripping towers in the treatment of groundwater polluted by municipal solid waste landfill leachate. Study of the causes of scaling and its effects on stripping performance / Incrustação das torres de arraste de amônia no tratamento de águas subterrâneas poluídas pelo chorume de aterro de resíduos sólidos urbanos. Estudo das causas da incrustação e seus efeitos na eficiência de extração
VIOTTI, Paolo;
2015
Abstract
This paper documents the causes of the scaling of stripping towers used for the treatment of groundwater polluted by the leachate from an old municipal solid waste (MSW) landfill in northern Italy. The effects of the scaling on the stripping performance are also reported. The whole process consists of a coagulation-flocculation pre-treatment at pH > 11, followed by an ammonia stripping stage, after heating the water to 38°C in order to improve removal efficiency. The stripped ammonia is recovered by absorption with sulfuric acid, producing a 30% solution of ammonium sulfate (reused as a base fertilizer). The effluent air stream is recirculated to the stripping towers (closed loop systems) in order to avoid an excessive temperature drop inside the packings, mainly in winter, with consequent loss of efficiency and risk of icing. The progressive scaling of the packing has resulted in a loss of ammonia removal efficiency from an initial value of 98% (clean packing) down to 80% after six months of continuous operation, necessitating a chemical cleaning. Optimum conditions for design and operation of the stripping process are also documented. © 2015, Institute for Environmental Research in Hydrographic Basins (IPABHi). All rights reserved.File | Dimensione | Formato | |
---|---|---|---|
Viotti_Scaling-ammonia-stripping_2015.pdf
accesso aperto
Note: http://www.scielo.br/scielo.php?pid=S1980-993X2015000200240&script=sci_abstract
Tipologia:
Documento in Post-print (versione successiva alla peer review e accettata per la pubblicazione)
Licenza:
Creative commons
Dimensione
930.49 kB
Formato
Adobe PDF
|
930.49 kB | Adobe PDF | Visualizza/Apri PDF |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.