This paper analyzes crane power supply, typical distribution schemes in typical container terminals, the different system grounding techniques and their impact on the service continuity of cranes. On the primary and secondary MV distribution systems, provided by loop configuration, service continuity can be achieved also by TN- systems, with automatic disconnection of supply, due to the power source redundancy. The MV supplying system of a crane (lines of tertiary distribution, devices, machinery) constitutes an equipment under control EUC that has to be guaranteed to achieve or maintain a safe and integer state in case of fault events. On crane MV power supply lines with radial structure, the possibility to ensure service continuity consists in choosing an IT-system with High Resistance Grounding HRG. In fact, the faulted line can stay on service after a ground fault during the short time necessary to maintain the service of the faulted crane and contemporary to try in solving the fault or to remove the same crane.

Neutral grounding in MV transformers substations for cranes service / Parise, Giuseppe; Parise, Luigi; Martufi, Marco; Su, Chun Lien; Chavdarian, Peniamin; Panetta, Sergio. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 52:3(2016), pp. 2070-2076. (Intervento presentato al convegno IEEE IAS ANNUAL MEETING 2015 tenutosi a DALLAS TX USA nel 18-22 OTTOBRE 2015) [10.1109/TIA.2016.2521726].

Neutral grounding in MV transformers substations for cranes service

PARISE, Giuseppe;PARISE, LUIGI;
2016

Abstract

This paper analyzes crane power supply, typical distribution schemes in typical container terminals, the different system grounding techniques and their impact on the service continuity of cranes. On the primary and secondary MV distribution systems, provided by loop configuration, service continuity can be achieved also by TN- systems, with automatic disconnection of supply, due to the power source redundancy. The MV supplying system of a crane (lines of tertiary distribution, devices, machinery) constitutes an equipment under control EUC that has to be guaranteed to achieve or maintain a safe and integer state in case of fault events. On crane MV power supply lines with radial structure, the possibility to ensure service continuity consists in choosing an IT-system with High Resistance Grounding HRG. In fact, the faulted line can stay on service after a ground fault during the short time necessary to maintain the service of the faulted crane and contemporary to try in solving the fault or to remove the same crane.
2016
Equipment under control, grounding systems, port, power system architecture, service continuity, terminalcontainer.
01 Pubblicazione su rivista::01a Articolo in rivista
Neutral grounding in MV transformers substations for cranes service / Parise, Giuseppe; Parise, Luigi; Martufi, Marco; Su, Chun Lien; Chavdarian, Peniamin; Panetta, Sergio. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 52:3(2016), pp. 2070-2076. (Intervento presentato al convegno IEEE IAS ANNUAL MEETING 2015 tenutosi a DALLAS TX USA nel 18-22 OTTOBRE 2015) [10.1109/TIA.2016.2521726].
File allegati a questo prodotto
File Dimensione Formato  
Parise_neutral_2016.pdf

solo gestori archivio

Note: articolo principale
Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.25 MB
Formato Adobe PDF
1.25 MB Adobe PDF   Contatta l'autore
Neutral grounding.pdf

solo gestori archivio

Note: articolo principale
Tipologia: Documento in Post-print (versione successiva alla peer review e accettata per la pubblicazione)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 621.43 kB
Formato Adobe PDF
621.43 kB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/874052
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 8
  • ???jsp.display-item.citation.isi??? 3
social impact