This paper analyzes crane power supply, typical distribution schemes in typical container terminals, the different system grounding techniques and their impact on the service continuity of cranes. On the primary and secondary MV distribution systems, provided by loop configuration, service continuity can be achieved also by TN- systems, with automatic disconnection of supply, due to the power source redundancy. The MV supplying system of a crane (lines of tertiary distribution, devices, machinery) constitutes an equipment under control EUC that has to be guaranteed to achieve or maintain a safe and integer state in case of fault events. On crane MV power supply lines with radial structure, the possibility to ensure service continuity consists in choosing an IT-system with High Resistance Grounding HRG. In fact, the faulted line can stay on service after a ground fault during the short time necessary to maintain the service of the faulted crane and contemporary to try in solving the fault or to remove the same crane.
Neutral grounding in MV transformers substations for cranes service / Parise, Giuseppe; Parise, Luigi; Martufi, Marco; Su, Chun Lien; Chavdarian, Peniamin; Panetta, Sergio. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 52:3(2016), pp. 2070-2076. (Intervento presentato al convegno IEEE IAS ANNUAL MEETING 2015 tenutosi a DALLAS TX USA nel 18-22 OTTOBRE 2015) [10.1109/TIA.2016.2521726].
Neutral grounding in MV transformers substations for cranes service
PARISE, Giuseppe;PARISE, LUIGI;
2016
Abstract
This paper analyzes crane power supply, typical distribution schemes in typical container terminals, the different system grounding techniques and their impact on the service continuity of cranes. On the primary and secondary MV distribution systems, provided by loop configuration, service continuity can be achieved also by TN- systems, with automatic disconnection of supply, due to the power source redundancy. The MV supplying system of a crane (lines of tertiary distribution, devices, machinery) constitutes an equipment under control EUC that has to be guaranteed to achieve or maintain a safe and integer state in case of fault events. On crane MV power supply lines with radial structure, the possibility to ensure service continuity consists in choosing an IT-system with High Resistance Grounding HRG. In fact, the faulted line can stay on service after a ground fault during the short time necessary to maintain the service of the faulted crane and contemporary to try in solving the fault or to remove the same crane.File | Dimensione | Formato | |
---|---|---|---|
Parise_neutral_2016.pdf
solo gestori archivio
Note: articolo principale
Tipologia:
Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza:
Tutti i diritti riservati (All rights reserved)
Dimensione
1.25 MB
Formato
Adobe PDF
|
1.25 MB | Adobe PDF | Contatta l'autore |
Neutral grounding.pdf
solo gestori archivio
Note: articolo principale
Tipologia:
Documento in Post-print (versione successiva alla peer review e accettata per la pubblicazione)
Licenza:
Tutti i diritti riservati (All rights reserved)
Dimensione
621.43 kB
Formato
Adobe PDF
|
621.43 kB | Adobe PDF | Contatta l'autore |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.