The undergrounding of HV subtransmission networks in urban/suburban areas is bound to increase fault currents, especially for ground faults if system neutral is solidly grounded. A parametric fault analysis based on symmetrical components is applied to a sample HV system with three lines and two EHV points of supply, based on a simple meshed Italian subtransmission network. Results are then validated by detailed three-phase ATP-EMTP simulations. Values yielded by the parametric study confirm the expected increase of all fault levels, reaching up to 36% and 69% for three-phase and 1-phase-to-ground faults, and even 104% for the ground current of phase-to-phase-to-ground faults. All calculated values are however tolerable, with fault currents well within the operating envelope of devices and components; cross-bonded sheaths also significantly relieve substation grounding mats. Some consequences of undergrounding such as reduction of earth-fault factor may be actually beneficial.

Fault current increase due to the progressive undergrounding of HV subtransmission network / Maddalena, Schembari; Codino, Asia; Catapano, A; Lauria, Stefano. - ELETTRONICO. - (2015), pp. 1403-1408. (Intervento presentato al convegno International Conference on Environment and Electrical Engineering tenutosi a Rome nel 10-13 June 2015) [10.1109/EEEIC.2015.7165375].

Fault current increase due to the progressive undergrounding of HV subtransmission network

CODINO, ASIA;LAURIA, Stefano
2015

Abstract

The undergrounding of HV subtransmission networks in urban/suburban areas is bound to increase fault currents, especially for ground faults if system neutral is solidly grounded. A parametric fault analysis based on symmetrical components is applied to a sample HV system with three lines and two EHV points of supply, based on a simple meshed Italian subtransmission network. Results are then validated by detailed three-phase ATP-EMTP simulations. Values yielded by the parametric study confirm the expected increase of all fault levels, reaching up to 36% and 69% for three-phase and 1-phase-to-ground faults, and even 104% for the ground current of phase-to-phase-to-ground faults. All calculated values are however tolerable, with fault currents well within the operating envelope of devices and components; cross-bonded sheaths also significantly relieve substation grounding mats. Some consequences of undergrounding such as reduction of earth-fault factor may be actually beneficial.
2015
International Conference on Environment and Electrical Engineering
fault currents; HV subtransmission networks; primary station grounding system; underground cables
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
Fault current increase due to the progressive undergrounding of HV subtransmission network / Maddalena, Schembari; Codino, Asia; Catapano, A; Lauria, Stefano. - ELETTRONICO. - (2015), pp. 1403-1408. (Intervento presentato al convegno International Conference on Environment and Electrical Engineering tenutosi a Rome nel 10-13 June 2015) [10.1109/EEEIC.2015.7165375].
File allegati a questo prodotto
File Dimensione Formato  
Schembari_Fault_2015.pdf

solo gestori archivio

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 865.24 kB
Formato Adobe PDF
865.24 kB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/849648
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 3
  • ???jsp.display-item.citation.isi??? 0
social impact