The undergrounding of HV subtransmission networks in urban/suburban areas is bound to increase fault currents, especially for ground faults if system neutral is solidly grounded. A parametric fault analysis based on symmetrical components is applied to a sample HV system with three lines and two EHV points of supply, based on a simple meshed Italian subtransmission network. Results are then validated by detailed three-phase ATP-EMTP simulations. Values yielded by the parametric study confirm the expected increase of all fault levels, reaching up to 36% and 69% for three-phase and 1-phase-to-ground faults, and even 104% for the ground current of phase-to-phase-to-ground faults. All calculated values are however tolerable, with fault currents well within the operating envelope of devices and components; cross-bonded sheaths also significantly relieve substation grounding mats. Some consequences of undergrounding such as reduction of earth-fault factor may be actually beneficial.
Fault current increase due to the progressive undergrounding of HV subtransmission network / Maddalena, Schembari; Codino, Asia; Catapano, A; Lauria, Stefano. - ELETTRONICO. - (2015), pp. 1403-1408. (Intervento presentato al convegno International Conference on Environment and Electrical Engineering tenutosi a Rome nel 10-13 June 2015) [10.1109/EEEIC.2015.7165375].
Fault current increase due to the progressive undergrounding of HV subtransmission network
CODINO, ASIA;LAURIA, Stefano
2015
Abstract
The undergrounding of HV subtransmission networks in urban/suburban areas is bound to increase fault currents, especially for ground faults if system neutral is solidly grounded. A parametric fault analysis based on symmetrical components is applied to a sample HV system with three lines and two EHV points of supply, based on a simple meshed Italian subtransmission network. Results are then validated by detailed three-phase ATP-EMTP simulations. Values yielded by the parametric study confirm the expected increase of all fault levels, reaching up to 36% and 69% for three-phase and 1-phase-to-ground faults, and even 104% for the ground current of phase-to-phase-to-ground faults. All calculated values are however tolerable, with fault currents well within the operating envelope of devices and components; cross-bonded sheaths also significantly relieve substation grounding mats. Some consequences of undergrounding such as reduction of earth-fault factor may be actually beneficial.File | Dimensione | Formato | |
---|---|---|---|
Schembari_Fault_2015.pdf
solo gestori archivio
Tipologia:
Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza:
Tutti i diritti riservati (All rights reserved)
Dimensione
865.24 kB
Formato
Adobe PDF
|
865.24 kB | Adobe PDF | Contatta l'autore |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.