When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighbouring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.

Current and voltage behaviour during a fault in a HV/MV system: Methods and measurements / Colella, P.; Napoli, R.; Pons, E.; Tommasini, R.; Barresi, A.; Cafaro, G.; De Simone, A.; Di Silvestre, M. L.; Martirano, Luigi; Montegiglio, P.; Morozova, E.; Parise, Giuseppe; Parise, Luigi; Riva Sanseverino, E.; Torelli, F.; Tummolillo, F.; Valtorta, G.; Zizzo, G.. - STAMPA. - 1:(2015), pp. 404-409. (Intervento presentato al convegno 15th IEEE International Conference on Environment and Electrical Engineering, EEEIC 2015 tenutosi a Rome, Italy nel 10-13 giugno 2015) [10.1109/EEEIC.2015.7165196].

Current and voltage behaviour during a fault in a HV/MV system: Methods and measurements

MARTIRANO, Luigi;PARISE, Giuseppe;PARISE, LUIGI;
2015

Abstract

When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighbouring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.
2015
15th IEEE International Conference on Environment and Electrical Engineering, EEEIC 2015
current distribution; electrical safety; global earthing systems; grounding; power distribution faults; single line to ground fault; electrical and electronic engineering; energy engineering and power technology
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
Current and voltage behaviour during a fault in a HV/MV system: Methods and measurements / Colella, P.; Napoli, R.; Pons, E.; Tommasini, R.; Barresi, A.; Cafaro, G.; De Simone, A.; Di Silvestre, M. L.; Martirano, Luigi; Montegiglio, P.; Morozova, E.; Parise, Giuseppe; Parise, Luigi; Riva Sanseverino, E.; Torelli, F.; Tummolillo, F.; Valtorta, G.; Zizzo, G.. - STAMPA. - 1:(2015), pp. 404-409. (Intervento presentato al convegno 15th IEEE International Conference on Environment and Electrical Engineering, EEEIC 2015 tenutosi a Rome, Italy nel 10-13 giugno 2015) [10.1109/EEEIC.2015.7165196].
File allegati a questo prodotto
File Dimensione Formato  
Colella∗_Current_2015.pdf

solo gestori archivio

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.67 MB
Formato Adobe PDF
1.67 MB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/822805
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 14
  • ???jsp.display-item.citation.isi??? 8
social impact