Nowadays companies supplying medium/high voltage electric energy, near residential areas, tend to use underground cables laying. Hence the design engineer is required to estimate the thermal resistance around the underground cable to perform a right dimensioning of the cables; as a matter of fact what it should be avoided is the overheating determined by a bad heat dissipation due to the Joule effect. IEC rules provides a formula for the evaluation of the soil thermal resistance which is easy to apply. But from an experimental point of view, as the bibliography shows, it was discovered it tends to underestimate the problem when dealing with very dry soils in particular. Thanks to an experimental system, some useful data were collected for the validation of a 2D FEM model of an excavated area with a linear heat source reproducing the underground conduit. The numerical model presents a variation of both the geometrical parameters of the excavated area and the distance characterizing other cables (hence heat sources) located in the same site of installation examined. In this way two dimensionless coefficients, useful to correct the values of the thermal resistance furnished by the current regulations, were determined.

Underground electric cables a correct evaluation of the soil thermal resistance / Salata, Ferdinando; Nardecchia, Fabio; DE LIETO VOLLARO, Andrea; Gugliermetti, Franco. - In: APPLIED THERMAL ENGINEERING. - ISSN 1359-4311. - STAMPA. - 78:(2015), pp. 268-277. [10.1016/j.applthermaleng.2014.12.059]

Underground electric cables a correct evaluation of the soil thermal resistance

SALATA, FERDINANDO;NARDECCHIA, FABIO;DE LIETO VOLLARO, Andrea;GUGLIERMETTI, Franco
2015

Abstract

Nowadays companies supplying medium/high voltage electric energy, near residential areas, tend to use underground cables laying. Hence the design engineer is required to estimate the thermal resistance around the underground cable to perform a right dimensioning of the cables; as a matter of fact what it should be avoided is the overheating determined by a bad heat dissipation due to the Joule effect. IEC rules provides a formula for the evaluation of the soil thermal resistance which is easy to apply. But from an experimental point of view, as the bibliography shows, it was discovered it tends to underestimate the problem when dealing with very dry soils in particular. Thanks to an experimental system, some useful data were collected for the validation of a 2D FEM model of an excavated area with a linear heat source reproducing the underground conduit. The numerical model presents a variation of both the geometrical parameters of the excavated area and the distance characterizing other cables (hence heat sources) located in the same site of installation examined. In this way two dimensionless coefficients, useful to correct the values of the thermal resistance furnished by the current regulations, were determined.
2015
CFD model; Design method; Dry soil; IEC 287; Linear heat source; Underground cable
01 Pubblicazione su rivista::01a Articolo in rivista
Underground electric cables a correct evaluation of the soil thermal resistance / Salata, Ferdinando; Nardecchia, Fabio; DE LIETO VOLLARO, Andrea; Gugliermetti, Franco. - In: APPLIED THERMAL ENGINEERING. - ISSN 1359-4311. - STAMPA. - 78:(2015), pp. 268-277. [10.1016/j.applthermaleng.2014.12.059]
File allegati a questo prodotto
File Dimensione Formato  
Salata_underground_2015.pdf

solo utenti autorizzati

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.83 MB
Formato Adobe PDF
1.83 MB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/780931
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 48
  • ???jsp.display-item.citation.isi??? 42
social impact