This paper discusses the design criteria for the electrical systems of roadway tunnels with particular regard to the safety in the daily operation and in the case of fire events. It proposes a fit distribution system and an adaptive criterion for the support lighting system in order to minimize costs and energy impact. Electric systems of roadway tunnels need sophisticated architecture to allow the presence of extensively distributed loads and more stringent installation requirements due to the presence of fire hazard. Mechanical and electrical design criteria must be based on equipment qualification categories (EQCs), which are characterized by thermal inherent resistance and environmental parameters. Design criteria must include variable configurations to simplify installation, allow flexible operation, and optimize the cost-benefit ratio. A special power distribution, herein defined as “brush distribution,” and a temperature zone classification are proposed for road tunnels with a higher risk in the case of a fire event. Therefore, this paper suggests as design parameters the temperature exposure levels characterizing the thermal demand in each zones and the EQCs in order to choose the equipment with adequate thermal resistance.

The Electrical Systems of Roadway Tunnels: Safety Design and Ecomanagement / Parise, Giuseppe; Martirano, Luigi; Parise, Luigi; L., Carrarini; M., Mitolo. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 51:2(2015), pp. 1920-1927. [10.1109/TIA.2014.2361173]

The Electrical Systems of Roadway Tunnels: Safety Design and Ecomanagement

PARISE, Giuseppe;MARTIRANO, Luigi;PARISE, LUIGI;
2015

Abstract

This paper discusses the design criteria for the electrical systems of roadway tunnels with particular regard to the safety in the daily operation and in the case of fire events. It proposes a fit distribution system and an adaptive criterion for the support lighting system in order to minimize costs and energy impact. Electric systems of roadway tunnels need sophisticated architecture to allow the presence of extensively distributed loads and more stringent installation requirements due to the presence of fire hazard. Mechanical and electrical design criteria must be based on equipment qualification categories (EQCs), which are characterized by thermal inherent resistance and environmental parameters. Design criteria must include variable configurations to simplify installation, allow flexible operation, and optimize the cost-benefit ratio. A special power distribution, herein defined as “brush distribution,” and a temperature zone classification are proposed for road tunnels with a higher risk in the case of a fire event. Therefore, this paper suggests as design parameters the temperature exposure levels characterizing the thermal demand in each zones and the EQCs in order to choose the equipment with adequate thermal resistance.
2015
road tunnels lighting; special installations; electricpower systems; fire hazard; energy savings
01 Pubblicazione su rivista::01a Articolo in rivista
The Electrical Systems of Roadway Tunnels: Safety Design and Ecomanagement / Parise, Giuseppe; Martirano, Luigi; Parise, Luigi; L., Carrarini; M., Mitolo. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 51:2(2015), pp. 1920-1927. [10.1109/TIA.2014.2361173]
File allegati a questo prodotto
File Dimensione Formato  
Parise_The-Electrical_2015.pdf

solo gestori archivio

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.04 MB
Formato Adobe PDF
1.04 MB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/631185
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 18
  • ???jsp.display-item.citation.isi??? 13
social impact