This paper presents a simplified model of arc fault that allows analyzing the dynamic behavior and evaluating the rms value of arcing fault current and the incident energy released by the electric arc. This study confirms previous results carried out in low-voltage and medium-voltage systems in different configurations, where the values of arcing fault current estimated by the simplified model are in accordance with the corresponding values determined by the equations described by IEEE Standard 1584. The dynamic behavior of the electric arc depends on a lot of factors. As improvement, the simplified model allows analyzing and determining basic parameters such as conduction angle, peak value, reduction factor of arc current, and power and energy supporting the understanding of the phenomenon of the arc flash. The behavior of the arc current conduction is predicted by knowledge of the phase angle of fault circuit impedance and the phase angle of the ignition voltage; the reduction factor of arc current is variable depending on whether the conduction is continuous or pulsating

Simplified Arc-Fault Model: The Reduction Factor of the Arc Current / Parise, Giuseppe; Martirano, Luigi; Marco, Laurini. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 49:(2013), pp. 1703-1710. [10.1109/TIA.2013.2256452]

Simplified Arc-Fault Model: The Reduction Factor of the Arc Current

PARISE, Giuseppe;MARTIRANO, Luigi;
2013

Abstract

This paper presents a simplified model of arc fault that allows analyzing the dynamic behavior and evaluating the rms value of arcing fault current and the incident energy released by the electric arc. This study confirms previous results carried out in low-voltage and medium-voltage systems in different configurations, where the values of arcing fault current estimated by the simplified model are in accordance with the corresponding values determined by the equations described by IEEE Standard 1584. The dynamic behavior of the electric arc depends on a lot of factors. As improvement, the simplified model allows analyzing and determining basic parameters such as conduction angle, peak value, reduction factor of arc current, and power and energy supporting the understanding of the phenomenon of the arc flash. The behavior of the arc current conduction is predicted by knowledge of the phase angle of fault circuit impedance and the phase angle of the ignition voltage; the reduction factor of arc current is variable depending on whether the conduction is continuous or pulsating
2013
arc fault; arc flash; circuit protection; safety; Short Circuit Current
01 Pubblicazione su rivista::01a Articolo in rivista
Simplified Arc-Fault Model: The Reduction Factor of the Arc Current / Parise, Giuseppe; Martirano, Luigi; Marco, Laurini. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 49:(2013), pp. 1703-1710. [10.1109/TIA.2013.2256452]
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/523304
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 62
  • ???jsp.display-item.citation.isi??? 43
social impact