At present several definitions of partial discharge inception voltage (PDIV) have been advanced by various interested groups. To establish the value of each of these definitions, four practical electrical insulating fluids were selected and their PDIV were determined according to three of these different specifications. The results of this study are presented and they suggest that the use of PDIV as a quality criterion generally is not warranted. The significance of these findings is discussed.
The effect of the definition used in measuring partial discharge inception voltages / Pompili, Massimo; MAZZETTI DI PIETRALATA, Carlo; M., Libotte; E. O., Forster. - In: IEEE TRANSACTIONS ON ELECTRICAL INSULATION. - ISSN 0018-9367. - STAMPA. - 28:6(1993), pp. 1002-1006. [10.1109/14.249373]
The effect of the definition used in measuring partial discharge inception voltages
POMPILI, Massimo;MAZZETTI DI PIETRALATA, Carlo;
1993
Abstract
At present several definitions of partial discharge inception voltage (PDIV) have been advanced by various interested groups. To establish the value of each of these definitions, four practical electrical insulating fluids were selected and their PDIV were determined according to three of these different specifications. The results of this study are presented and they suggest that the use of PDIV as a quality criterion generally is not warranted. The significance of these findings is discussed.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.