The paper describes an experimental plant aimed at simulating and verifying the performances of a single-stage H2O-LiBr absorption machine. The machine is water cooled and it is supplied by hot water produced by an electrical boiler, it is possible to simulate different service conditions by varying the temperatures and the flow rate of water in the external circuits. Measurement facilities allow to record in real time all the main operating parameters of internal and external circuits (temperatures, pressures and flow rates). The paper illustrates the characteristics of the machine and of the plant and the results of various experimental campaigns. In particular, the acquisitions on the plant have tested different service conditions by varying the flow rate and the supplying hot water; the energy and energy performances of the plant are presented and compared with data from literature and from a simulation code developed for the plant. The results show that the absorption machine can work, with acceptable efficiency, with input temperatures of about 65-70 °C; this results is interesting for a future supply of the machine with solar energy.

EXPERIMENTAL EVALUATION OF THE PERFORMANCES OF H2O- LiBr ABSORPTION REFRIGERATOR UNDER SERVICE CONDITION / Grignaffini, Stefano; F., Asdrubali. - In: INTERNATIONAL JOURNAL OF REFRIGERATION. - ISSN 0140-7007. - 28, Number 4:(2005), pp. 489-497. [10.1016/j.ijrefrig.2004.11.006]

EXPERIMENTAL EVALUATION OF THE PERFORMANCES OF H2O- LiBr ABSORPTION REFRIGERATOR UNDER SERVICE CONDITION

GRIGNAFFINI, Stefano;
2005

Abstract

The paper describes an experimental plant aimed at simulating and verifying the performances of a single-stage H2O-LiBr absorption machine. The machine is water cooled and it is supplied by hot water produced by an electrical boiler, it is possible to simulate different service conditions by varying the temperatures and the flow rate of water in the external circuits. Measurement facilities allow to record in real time all the main operating parameters of internal and external circuits (temperatures, pressures and flow rates). The paper illustrates the characteristics of the machine and of the plant and the results of various experimental campaigns. In particular, the acquisitions on the plant have tested different service conditions by varying the flow rate and the supplying hot water; the energy and energy performances of the plant are presented and compared with data from literature and from a simulation code developed for the plant. The results show that the absorption machine can work, with acceptable efficiency, with input temperatures of about 65-70 °C; this results is interesting for a future supply of the machine with solar energy.
2005
01 Pubblicazione su rivista::01a Articolo in rivista
EXPERIMENTAL EVALUATION OF THE PERFORMANCES OF H2O- LiBr ABSORPTION REFRIGERATOR UNDER SERVICE CONDITION / Grignaffini, Stefano; F., Asdrubali. - In: INTERNATIONAL JOURNAL OF REFRIGERATION. - ISSN 0140-7007. - 28, Number 4:(2005), pp. 489-497. [10.1016/j.ijrefrig.2004.11.006]
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/45505
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 62
  • ???jsp.display-item.citation.isi??? 53
social impact