This paper provides a summary of the IEC protection against electric shock. This protection is provided by appropriate basic measures as follows: (1) for protection both in normal service and in case of a fault (against both direct and indirect contact), use low and safe voltage of 50 V and below; (2) for protection in normal service (against direct contact), use insulation and/or enclose live parts or use isolation distance; and (3) for protection in case of a fault (against indirect contact), prevent conducting parts not normally energized from becoming live. This is accomplished by grounding and automatic disconnection of the supply, by use of Class II equipment (as double or equivalent insulation), or by separating the supply from ground, IEC publication 364-4-41 “Electrical installations of buildings”, (Part 4, Chapter 41) classifies types of system grounding as TN-system, TT-system, and IT-system. Development of this summary is based on actual hazard risk analysis of potential incidents to suggest criterion by which the appropriate measures can be applied to avoid or mitigate injury or damage

A summary on the IEC protection against electric shock / Parise, Giuseppe. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 34 issue:5:(1998), pp. 911-922. [10.1109/28.720429]

A summary on the IEC protection against electric shock

PARISE, Giuseppe
1998

Abstract

This paper provides a summary of the IEC protection against electric shock. This protection is provided by appropriate basic measures as follows: (1) for protection both in normal service and in case of a fault (against both direct and indirect contact), use low and safe voltage of 50 V and below; (2) for protection in normal service (against direct contact), use insulation and/or enclose live parts or use isolation distance; and (3) for protection in case of a fault (against indirect contact), prevent conducting parts not normally energized from becoming live. This is accomplished by grounding and automatic disconnection of the supply, by use of Class II equipment (as double or equivalent insulation), or by separating the supply from ground, IEC publication 364-4-41 “Electrical installations of buildings”, (Part 4, Chapter 41) classifies types of system grounding as TN-system, TT-system, and IT-system. Development of this summary is based on actual hazard risk analysis of potential incidents to suggest criterion by which the appropriate measures can be applied to avoid or mitigate injury or damage
1998
Class II equipment; TN-system; TT-system; IT-system; direct and indirect contact
01 Pubblicazione su rivista::01a Articolo in rivista
A summary on the IEC protection against electric shock / Parise, Giuseppe. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 34 issue:5:(1998), pp. 911-922. [10.1109/28.720429]
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/28807
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 39
  • ???jsp.display-item.citation.isi??? 28
social impact