In electrical power systems bolted short-circuits are rare and the fault usually involves arcing and burning; mostly the limit value of minimum short-circuit depends really on arcing-fault. In AC low voltage systems, the paper examines the arcing-fault branch circuits as weak points. Different protection measures are available against the arc-faults. A first measure that can guarantee a probabilistic protection is allowed by the adoption of overcurrent protective devices (OCPD), optimizing the design of the structure of the system and/or the coordination of protection. A well known complete protection is allowed by adopting are-fault circuit interrupters (AFCI) for the protection of branch circuits. The authors suggest a new complete protection allowed wiring the branch circuits, including particularly extension cords, with special power cables, protected by ordinary ground fault protective devices (GFPD). The suggested design for single-core or multi-core power cables is that each insulated core has a concentric conductor shield. Converting the line-to-line fault into a line to ground fault or into a mixed type is the goal of this special cable type Faults Ground-Forced Cable (FGFC).

The arc-fault circuit protection / Parise, Giuseppe; Martirano, Luigi; Grasselli, Umberto; L., Benetti. - STAMPA. - 3:(2001), pp. 1817-1822. (Intervento presentato al convegno 36th Annual Meeting of the Industry-Application-Society (IAS) tenutosi a CHICAGO, IL nel SEP 30-OCT 04, 2000) [10.1109/ias.2001.955778].

The arc-fault circuit protection

PARISE, Giuseppe;MARTIRANO, Luigi;GRASSELLI, Umberto;
2001

Abstract

In electrical power systems bolted short-circuits are rare and the fault usually involves arcing and burning; mostly the limit value of minimum short-circuit depends really on arcing-fault. In AC low voltage systems, the paper examines the arcing-fault branch circuits as weak points. Different protection measures are available against the arc-faults. A first measure that can guarantee a probabilistic protection is allowed by the adoption of overcurrent protective devices (OCPD), optimizing the design of the structure of the system and/or the coordination of protection. A well known complete protection is allowed by adopting are-fault circuit interrupters (AFCI) for the protection of branch circuits. The authors suggest a new complete protection allowed wiring the branch circuits, including particularly extension cords, with special power cables, protected by ordinary ground fault protective devices (GFPD). The suggested design for single-core or multi-core power cables is that each insulated core has a concentric conductor shield. Converting the line-to-line fault into a line to ground fault or into a mixed type is the goal of this special cable type Faults Ground-Forced Cable (FGFC).
2001
36th Annual Meeting of the Industry-Application-Society (IAS)
arc fault; circuit protection; low voltage systems
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
The arc-fault circuit protection / Parise, Giuseppe; Martirano, Luigi; Grasselli, Umberto; L., Benetti. - STAMPA. - 3:(2001), pp. 1817-1822. (Intervento presentato al convegno 36th Annual Meeting of the Industry-Application-Society (IAS) tenutosi a CHICAGO, IL nel SEP 30-OCT 04, 2000) [10.1109/ias.2001.955778].
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/251826
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 25
  • ???jsp.display-item.citation.isi??? 7
social impact