The paper deals with the performance during ground faults of MV/LV substation grounding systems belonging to a “Common Grounding System” as per CENELEC HD 637 S1–1999 E. A parametric analysis is performed, by means of ATP-EMTP, on a typical 150/20/0.4 kV distribution system, considering the MV neutral ungrounded or resonant-grounded. Results obtained highlight the benefits brought by the Common Grounding System but also fault conditions, such as double-earth-fault on MV line(s) or 1-Phase-to-Ground fault HV side in the HV/MV substation, which can still generate significant touch and step voltages that should not be disregarded in the system grounding design.

Performance of the common grounding system during ground faults / Gatta, Fabio Massimo; Lauria, Stefano; Parise, Giuseppe; DEL GROSSO, D.. - STAMPA. - SESSIONE 2:(2005), pp. 1-5. (Intervento presentato al convegno 18th International Conference on Electricity Distribution tenutosi a Torino- Italia nel 6-9 Giugno 2005).

Performance of the common grounding system during ground faults

GATTA, Fabio Massimo;LAURIA, Stefano;PARISE, Giuseppe;
2005

Abstract

The paper deals with the performance during ground faults of MV/LV substation grounding systems belonging to a “Common Grounding System” as per CENELEC HD 637 S1–1999 E. A parametric analysis is performed, by means of ATP-EMTP, on a typical 150/20/0.4 kV distribution system, considering the MV neutral ungrounded or resonant-grounded. Results obtained highlight the benefits brought by the Common Grounding System but also fault conditions, such as double-earth-fault on MV line(s) or 1-Phase-to-Ground fault HV side in the HV/MV substation, which can still generate significant touch and step voltages that should not be disregarded in the system grounding design.
2005
18th International Conference on Electricity Distribution
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
Performance of the common grounding system during ground faults / Gatta, Fabio Massimo; Lauria, Stefano; Parise, Giuseppe; DEL GROSSO, D.. - STAMPA. - SESSIONE 2:(2005), pp. 1-5. (Intervento presentato al convegno 18th International Conference on Electricity Distribution tenutosi a Torino- Italia nel 6-9 Giugno 2005).
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/237459
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 6
  • ???jsp.display-item.citation.isi??? ND
social impact