Two-pole synchronous generators are high power machines (turbo-generators) used in generating plants, needing careful monitoring to avoid costly faults. The rotors may fail due to mechanical unbalances. Rotor eccentricities make rise unbalances in the stator armature split-phase currents. This paper shows original experimental proofs of a diagnosis method based on symmetrical components analysis in 2-pole machines and FFT spectral analysis of 4-pole complex sequence currents carried out from split-phase currents. The split-phase current signature analysis is applied in a practical on-line monitoring system implemented by virtual instrument on a laboratory 27kVA two-pole generator with mixed eccentricity and various voltage levels. The results show very good agreement between the theoretical previsions and the experiments.
Application technique for on-line monitoring of rotor eccentricities in two-pole synchronous generators by using the split-phase currents / Bruzzese, C.. - (2025), pp. 212-217. (9th International Conference on Power and Energy Engineering, ICPEE 2025 Chengdu; China ) [10.1109/icpee67608.2025.11422065].
Application technique for on-line monitoring of rotor eccentricities in two-pole synchronous generators by using the split-phase currents
Bruzzese, Claudio
Primo
Writing – Original Draft Preparation
2025
Abstract
Two-pole synchronous generators are high power machines (turbo-generators) used in generating plants, needing careful monitoring to avoid costly faults. The rotors may fail due to mechanical unbalances. Rotor eccentricities make rise unbalances in the stator armature split-phase currents. This paper shows original experimental proofs of a diagnosis method based on symmetrical components analysis in 2-pole machines and FFT spectral analysis of 4-pole complex sequence currents carried out from split-phase currents. The split-phase current signature analysis is applied in a practical on-line monitoring system implemented by virtual instrument on a laboratory 27kVA two-pole generator with mixed eccentricity and various voltage levels. The results show very good agreement between the theoretical previsions and the experiments.| File | Dimensione | Formato | |
|---|---|---|---|
|
Bruzzese_Application Technique for On-Line_2025.pdf
solo gestori archivio
Tipologia:
Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza:
Tutti i diritti riservati (All rights reserved)
Dimensione
9.4 MB
Formato
Adobe PDF
|
9.4 MB | Adobe PDF | Contatta l'autore |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.