The vigorous development of renewable power plants requires the installation of medium-voltage underground cable networks for the wiring of internal skids and the grid connection. Given the complexity of these networks, which are typically extensive and include a high number of joints, the required pre-commissioning tests should follow a pragmatic engineering approach and be completed within a reasonable timeframe. This paper focuses on field testing procedures for medium-voltage cables prior to energization, including electric resistance, oversheath integrity, and insulation integrity tests. For each test, key performance indicators are described in detail, along with acceptable variability ranges to support the accurate interpretation of results in practical applications. The implementation of the tests on the medium-voltage network of a photovoltaic plant in southern Italy is presented as a real-world application of the proposed assessment procedures.

Smart Tests for Medium Voltage Cables in Renewable Energy Plants: The Case Study of a PV Plant Located in Italy / Lorenzo, G.D., Stracqualursi, E., Araneo, R., Cecere, R.. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - 62:5(2026), pp. 7715-7725. [10.1109/TIA.2026.3661946]

Smart Tests for Medium Voltage Cables in Renewable Energy Plants: The Case Study of a PV Plant Located in Italy

Stracqualursi E.;Araneo R.;
2026

Abstract

The vigorous development of renewable power plants requires the installation of medium-voltage underground cable networks for the wiring of internal skids and the grid connection. Given the complexity of these networks, which are typically extensive and include a high number of joints, the required pre-commissioning tests should follow a pragmatic engineering approach and be completed within a reasonable timeframe. This paper focuses on field testing procedures for medium-voltage cables prior to energization, including electric resistance, oversheath integrity, and insulation integrity tests. For each test, key performance indicators are described in detail, along with acceptable variability ranges to support the accurate interpretation of results in practical applications. The implementation of the tests on the medium-voltage network of a photovoltaic plant in southern Italy is presented as a real-world application of the proposed assessment procedures.
2026
Damage detection; field measurement; medium voltage network; underground cables
01 Pubblicazione su rivista::01a Articolo in rivista
Smart Tests for Medium Voltage Cables in Renewable Energy Plants: The Case Study of a PV Plant Located in Italy / Lorenzo, G.D., Stracqualursi, E., Araneo, R., Cecere, R.. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - 62:5(2026), pp. 7715-7725. [10.1109/TIA.2026.3661946]
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/1776724
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? 0
social impact