Small groups of islands can be connected to the transmission grid through HVAC submarine cable line (CLs). Since the tourism sector has often a prominent role in their overall economy, the marked seasonal variation of the energy demand leads to an immediate impact on the cable loading. In low-load conditions, power losses along the cable are largely associated to its own charging currents. Power losses due to shunt reactors placed at both ends of the line are also considerable. Consequently, when low power flows are involved, the operation of the system at reduced voltages is required. The paper evaluates the opportunity of minimizing power losses as the transmitted active power changes by using Interconnection Transformers equipped with On-Load Tap Changers (OLTCs). The proposed solution aims to provide an accurate degree of control of the terminal voltages through the coordinated action of such devices.
HVAC Submarine Cables Optimization Transmission Strategies / Ciniello, Vincenzo; Loggia, Riccardo; Calcara, Luigi; Pompili, Massimo; Martirano, Luigi; Lauria, Stefano. - (2024), pp. 01-06. (Intervento presentato al convegno 24th EEEIC International Conference on Environment and Electrical Engineering and 8th I and CPS Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2024 tenutosi a Sapienza University of Rome, Faculty of Engineering, Via Eudossiana, 18, ita) [10.1109/eeeic/icpseurope61470.2024.10751016].
HVAC Submarine Cables Optimization Transmission Strategies
Ciniello, Vincenzo;Loggia, Riccardo
;Calcara, Luigi;Pompili, Massimo;Martirano, Luigi;Lauria, Stefano
2024
Abstract
Small groups of islands can be connected to the transmission grid through HVAC submarine cable line (CLs). Since the tourism sector has often a prominent role in their overall economy, the marked seasonal variation of the energy demand leads to an immediate impact on the cable loading. In low-load conditions, power losses along the cable are largely associated to its own charging currents. Power losses due to shunt reactors placed at both ends of the line are also considerable. Consequently, when low power flows are involved, the operation of the system at reduced voltages is required. The paper evaluates the opportunity of minimizing power losses as the transmitted active power changes by using Interconnection Transformers equipped with On-Load Tap Changers (OLTCs). The proposed solution aims to provide an accurate degree of control of the terminal voltages through the coordinated action of such devices.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.