In the companion Part I, the theory relevant to the role of shield wires in mitigating lightning-induced overvoltages in overhead lines has been analyzed and clarified. A more consistent meaning has been assigned to the concept of Shielding Factor by introducing two innovations compared to the current literature: the first one concerning the distinction between internal and external parameters, and the other one concerning the point along the line where to assess the mitigation effect. Thanks to this new approach, uncertainties seen in the literature have been sorted out, and the Shielding Factor has been shown to be a parameter which can be precisely quantified. However, our new contribution was applied to a schematic (unrealistic) configuration: a line with a shield wire grounded at only one point. This Part II is precisely devoted to confirming the results obtained in Part I, by applying the proposed approach to more realistic and practical line configurations, namely a line with multi-grounded shield wire, and a line equipped with laterals too.
On the role of shield wires in mitigating lightning-induced overvoltages in overhead lines. Part II: Simulation results for practical configurations / Andreotti, A.; Araneo, R.; Faria, J. B.; He, J.; Petrache, E.; Pierno, A.; Stracqualursi, E.. - In: IEEE TRANSACTIONS ON POWER DELIVERY. - ISSN 0885-8977. - 38:1(2023), pp. 1-9. [10.1109/TPWRD.2022.3189309]
On the role of shield wires in mitigating lightning-induced overvoltages in overhead lines. Part II: Simulation results for practical configurations
Araneo R.;Stracqualursi E.
2023
Abstract
In the companion Part I, the theory relevant to the role of shield wires in mitigating lightning-induced overvoltages in overhead lines has been analyzed and clarified. A more consistent meaning has been assigned to the concept of Shielding Factor by introducing two innovations compared to the current literature: the first one concerning the distinction between internal and external parameters, and the other one concerning the point along the line where to assess the mitigation effect. Thanks to this new approach, uncertainties seen in the literature have been sorted out, and the Shielding Factor has been shown to be a parameter which can be precisely quantified. However, our new contribution was applied to a schematic (unrealistic) configuration: a line with a shield wire grounded at only one point. This Part II is precisely devoted to confirming the results obtained in Part I, by applying the proposed approach to more realistic and practical line configurations, namely a line with multi-grounded shield wire, and a line equipped with laterals too.File | Dimensione | Formato | |
---|---|---|---|
Andreotti_On the Role_2023.pdf
accesso aperto
Note: Articolo pubblicato
Tipologia:
Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza:
Creative commons
Dimensione
3.91 MB
Formato
Adobe PDF
|
3.91 MB | Adobe PDF |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.