In electrical power systems, cords and extension cords are exposed to mechanical damage and other insulation stresses. Mechanical damage to stranded conductors can reduce locally their cross section or break them and cause anomalous local conditions of overheating or arcing. The ordinary protective devices cannot detect the series faults that persist, so the fault point remains energized and is subject to electric shock and fire hazards. Effective protection can be accomplished by implementing active and passive measures: installing arc-fault circuit interrupters or arc-fault detection devices, able to detect arcing faults, or wiring the circuits with a grounding protection conductor to involve the ground in every fault. In this way, residual current protective devices (residual current devices or ground fault protective devices) quickly protect the series faults not only with arc, but also without it. Ground-fault-forced cables facilitate by design the conversion of any kind of cable fault to a ground fault. They are particularly recommended for cords and extension cords, internal circuits to grounded equipment, uninterruptible power system continuity circuits, aircraft circuits, road tunnels, data centers, refrigerated containers parks, residences, and hospitals.
Measures to Minimize Series Faults in Electrical Cords and Extension Cords / Parise, Giuseppe; Hesla, Erling; Mardegan, Claudio Sergio; Parise, Luigi; Capaccini, Elisabetta Bragagni. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - 55:5(2019), pp. 4551-4556. (Intervento presentato al convegno 55th Industrial and Commercial Power Systems Technical Conference IEEE/IAS tenutosi a Calgary (Canada)) [10.1109/TIA.2019.2926240].
Measures to Minimize Series Faults in Electrical Cords and Extension Cords
Parise, Giuseppe
;Parise, Luigi;
2019
Abstract
In electrical power systems, cords and extension cords are exposed to mechanical damage and other insulation stresses. Mechanical damage to stranded conductors can reduce locally their cross section or break them and cause anomalous local conditions of overheating or arcing. The ordinary protective devices cannot detect the series faults that persist, so the fault point remains energized and is subject to electric shock and fire hazards. Effective protection can be accomplished by implementing active and passive measures: installing arc-fault circuit interrupters or arc-fault detection devices, able to detect arcing faults, or wiring the circuits with a grounding protection conductor to involve the ground in every fault. In this way, residual current protective devices (residual current devices or ground fault protective devices) quickly protect the series faults not only with arc, but also without it. Ground-fault-forced cables facilitate by design the conversion of any kind of cable fault to a ground fault. They are particularly recommended for cords and extension cords, internal circuits to grounded equipment, uninterruptible power system continuity circuits, aircraft circuits, road tunnels, data centers, refrigerated containers parks, residences, and hospitals.File | Dimensione | Formato | |
---|---|---|---|
Parise_Measures-to-minimize_2019.pdf
solo gestori archivio
Tipologia:
Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza:
Tutti i diritti riservati (All rights reserved)
Dimensione
1.19 MB
Formato
Adobe PDF
|
1.19 MB | Adobe PDF | Contatta l'autore |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.