This paper discusses of electrical distribution for refrigerated containers (reefers) in port terminals, characterized as parks of distributed loads. Power systems of uniform distributed loads (UDLs) need configurations with modularity whenever possible, to ensure an easier installation, management and maintenance, significant cost reductions, quality control. The cases of UDLs are present in many applications, both active and passive, ranging from racks of reefers, recharging battery banks of E-Trucks to the strings of a photovoltaic park. The paper suggests simple designing criteria, generally not applied in the ports, consisting in the adoption of a main MV distribution loop for the reefers parks, where in apposite container for each rack or group of racks, transformers supply locally a modular LV distribution to the reefers. This approach offers a relevant flexibility for expansions and endorses development of new fitting components.

Systems design criteria for uniformly distributed loads / Parise, G.; Parise, L.; Ruggiero, M. Di; Falanga, G.; Su, Chun-Lien; Chavdarian, P. B.. - (2018), pp. 1-6. (Intervento presentato al convegno 2018 IEEE Industry Applications Society Annual Meeting (IAS) tenutosi a Portland, OR, USA) [10.1109/IAS.2018.8544487].

Systems design criteria for uniformly distributed loads

Parise, G.;Parise, L.;
2018

Abstract

This paper discusses of electrical distribution for refrigerated containers (reefers) in port terminals, characterized as parks of distributed loads. Power systems of uniform distributed loads (UDLs) need configurations with modularity whenever possible, to ensure an easier installation, management and maintenance, significant cost reductions, quality control. The cases of UDLs are present in many applications, both active and passive, ranging from racks of reefers, recharging battery banks of E-Trucks to the strings of a photovoltaic park. The paper suggests simple designing criteria, generally not applied in the ports, consisting in the adoption of a main MV distribution loop for the reefers parks, where in apposite container for each rack or group of racks, transformers supply locally a modular LV distribution to the reefers. This approach offers a relevant flexibility for expansions and endorses development of new fitting components.
2018
2018 IEEE Industry Applications Society Annual Meeting (IAS)
port productivity , power system architecture , reefers , e-trucks , loads park
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
Systems design criteria for uniformly distributed loads / Parise, G.; Parise, L.; Ruggiero, M. Di; Falanga, G.; Su, Chun-Lien; Chavdarian, P. B.. - (2018), pp. 1-6. (Intervento presentato al convegno 2018 IEEE Industry Applications Society Annual Meeting (IAS) tenutosi a Portland, OR, USA) [10.1109/IAS.2018.8544487].
File allegati a questo prodotto
File Dimensione Formato  
Parise_system-design_2018.pdf

solo gestori archivio

Note: https://ieeexplore.ieee.org/document/8544487
Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 549.97 kB
Formato Adobe PDF
549.97 kB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/1211795
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 3
  • ???jsp.display-item.citation.isi??? 1
social impact