The paper proposes a novel approach to modelling time-varying non-linear loads in power systems, based on demand conditions. The model allows a pre-evaluation of harmonic disturbances under variable conditions using normal and uniform distribution to randomize the electrical values of the non-linear loads and the related harmonic spectra. A measurement campaign conducted on an industrial area, a deposit/maintenance and repair site utilized for trains in operation on the metro line B of Rome, has been taken into account to verify the model performance. The methodology allows estimating the voltage total harmonic distortion at the point of common coupling. Through a statistical analysis, the harmonic distortion distribution via common normality tests was evaluated. The procedure has been used also to a harmonic disturbance pre-evaluation due to a future introduction of electric vehicles charging stations in the area.

A Simulink model to assess harmonic distortion in MV/LV distribution networks with time-varying non linear loads / Lamedica, Regina; Ruvio, Alessandro; Ribeiro, Paulo Fernando; Regoli, Massimo. - In: SIMULATION MODELLING PRACTICE AND THEORY. - ISSN 1569-190X. - 90:(2019), pp. 64-80. [10.1016/j.simpat.2018.10.012]

A Simulink model to assess harmonic distortion in MV/LV distribution networks with time-varying non linear loads

Lamedica, Regina;Ruvio, Alessandro
;
2019

Abstract

The paper proposes a novel approach to modelling time-varying non-linear loads in power systems, based on demand conditions. The model allows a pre-evaluation of harmonic disturbances under variable conditions using normal and uniform distribution to randomize the electrical values of the non-linear loads and the related harmonic spectra. A measurement campaign conducted on an industrial area, a deposit/maintenance and repair site utilized for trains in operation on the metro line B of Rome, has been taken into account to verify the model performance. The methodology allows estimating the voltage total harmonic distortion at the point of common coupling. Through a statistical analysis, the harmonic distortion distribution via common normality tests was evaluated. The procedure has been used also to a harmonic disturbance pre-evaluation due to a future introduction of electric vehicles charging stations in the area.
2019
Harmonic distortions, Model, Power quality, Simulink, Statistical, Time varying harmonics, Variable loads
01 Pubblicazione su rivista::01a Articolo in rivista
A Simulink model to assess harmonic distortion in MV/LV distribution networks with time-varying non linear loads / Lamedica, Regina; Ruvio, Alessandro; Ribeiro, Paulo Fernando; Regoli, Massimo. - In: SIMULATION MODELLING PRACTICE AND THEORY. - ISSN 1569-190X. - 90:(2019), pp. 64-80. [10.1016/j.simpat.2018.10.012]
File allegati a questo prodotto
File Dimensione Formato  
Lamedica_postprint_Simulink_2019.pdf

solo gestori archivio

Tipologia: Documento in Post-print (versione successiva alla peer review e accettata per la pubblicazione)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.75 MB
Formato Adobe PDF
1.75 MB Adobe PDF   Contatta l'autore
Lamedica_Simulink_2019.pdf

solo gestori archivio

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 5.35 MB
Formato Adobe PDF
5.35 MB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/1211482
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 12
  • ???jsp.display-item.citation.isi??? 12
social impact