This study illustrates how selected instrument voltage transformers (VTs-I) behave in a transitory state. Some laboratory tests are conducted on medium voltage (MV) inductive voltage types to evaluate the voltage transferred from primary to secondary windings when a fast voltage impulse (1.2/50 μs) excites three machines constructively in different ways. Possible effects of metal parts present in the laboratory on the VTs-I behavior are analyzed, and other tests are conducted to determine a suitable shielding for the VTs-I. In order to interpret the experimental results, a theoretical study is performed using a simplified model of the instrument transformer. Finally, characteristic parameters are assigned values that were derived from experimental tests.

Transient-state analysis of MV instrument transformers / Lamedica, R.; Pompili, M.; Sangiovanni, S.; Calcara, L.; Ruvio, A.; Cauzillo, B. A.. - In: ELECTRIC POWER SYSTEMS RESEARCH. - ISSN 0378-7796. - 168:(2019), pp. 162-168. [10.1016/j.epsr.2018.11.015]

Transient-state analysis of MV instrument transformers

Lamedica, R.
;
Pompili, M.;Sangiovanni, S.;Calcara, L.;Ruvio, A.;
2019

Abstract

This study illustrates how selected instrument voltage transformers (VTs-I) behave in a transitory state. Some laboratory tests are conducted on medium voltage (MV) inductive voltage types to evaluate the voltage transferred from primary to secondary windings when a fast voltage impulse (1.2/50 μs) excites three machines constructively in different ways. Possible effects of metal parts present in the laboratory on the VTs-I behavior are analyzed, and other tests are conducted to determine a suitable shielding for the VTs-I. In order to interpret the experimental results, a theoretical study is performed using a simplified model of the instrument transformer. Finally, characteristic parameters are assigned values that were derived from experimental tests.
2019
Fast transient, Inductive voltage transformers, Measurements, Theoretical model
01 Pubblicazione su rivista::01a Articolo in rivista
Transient-state analysis of MV instrument transformers / Lamedica, R.; Pompili, M.; Sangiovanni, S.; Calcara, L.; Ruvio, A.; Cauzillo, B. A.. - In: ELECTRIC POWER SYSTEMS RESEARCH. - ISSN 0378-7796. - 168:(2019), pp. 162-168. [10.1016/j.epsr.2018.11.015]
File allegati a questo prodotto
File Dimensione Formato  
Lamedica_postprint_transient-State_2019.pdf

solo gestori archivio

Tipologia: Documento in Post-print (versione successiva alla peer review e accettata per la pubblicazione)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.09 MB
Formato Adobe PDF
1.09 MB Adobe PDF   Contatta l'autore
Lamedica_transient-state_2019.pdf

solo gestori archivio

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 1.62 MB
Formato Adobe PDF
1.62 MB Adobe PDF   Contatta l'autore

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/1211471
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? 2
social impact