Street lighting installations are publicly accessible electrical pieces of equipment out of the physical control of who operates/owns them. Street lighting systems are a typical case of low-voltage loads, distributed in a large area and collectively protected by the same protective device. In fault conditions, hazardous potentials may appear on the metal parts of such equipment, and expose persons to shock hazards. To reduce such risk, different solutions for the grounding are available. The Standard IEC 60364, and a current worldwide tendency, seem to encourage the use of Class II components, that is, equipment with double or reinforced insulation, for all the elements of the street light system (i.e. wiring systems, light fixtures, etc.). These authors examine possible technical alternatives in light of IEC standards, and propose to increase the safety of Class II metal poles by adopting a circuitry within lighting systems panelboards to monitor their double insulation-to-ground.

Grounding of Distributed LV Loads: the Street-Lighting Systems / Parise, Giuseppe; Martirano, Luigi; Mitolo, M; Baldwin, T; Panetta, S.. - STAMPA. - (2010), pp. 1-7. (Intervento presentato al convegno IEEE 2010 I&CPS tenutosi a Tallhassee, Florida, USA nel May 9-13 2010) [10.1109/ICPS.2010.5489893].

Grounding of Distributed LV Loads: the Street-Lighting Systems

PARISE, Giuseppe;MARTIRANO, Luigi;
2010

Abstract

Street lighting installations are publicly accessible electrical pieces of equipment out of the physical control of who operates/owns them. Street lighting systems are a typical case of low-voltage loads, distributed in a large area and collectively protected by the same protective device. In fault conditions, hazardous potentials may appear on the metal parts of such equipment, and expose persons to shock hazards. To reduce such risk, different solutions for the grounding are available. The Standard IEC 60364, and a current worldwide tendency, seem to encourage the use of Class II components, that is, equipment with double or reinforced insulation, for all the elements of the street light system (i.e. wiring systems, light fixtures, etc.). These authors examine possible technical alternatives in light of IEC standards, and propose to increase the safety of Class II metal poles by adopting a circuitry within lighting systems panelboards to monitor their double insulation-to-ground.
2010
IEEE 2010 I&CPS
electrical safety; lighting systems; street lighting
04 Pubblicazione in atti di convegno::04b Atto di convegno in volume
Grounding of Distributed LV Loads: the Street-Lighting Systems / Parise, Giuseppe; Martirano, Luigi; Mitolo, M; Baldwin, T; Panetta, S.. - STAMPA. - (2010), pp. 1-7. (Intervento presentato al convegno IEEE 2010 I&CPS tenutosi a Tallhassee, Florida, USA nel May 9-13 2010) [10.1109/ICPS.2010.5489893].
File allegati a questo prodotto
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/228217
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? 0
social impact