The failure of an emergency diesel generator could cause a blackout with economic or human losses, especially if it occurs in a hospital. The authors performed an up to date statistic on diesel generators fails has been investigated in a hundred of hospitals. Although standard maintenance operation has been correctly performed, it has been found a 6 % of failures for the genset per year. MTBF of generators and main components have been investigated and updated values are reported in this paper. Components reliability is proved to be at its maximum technological value, consequently an innovative solution is here proposed. Often neighboring buildings or different electrical systems have separated emergency generators. Nowadays, in case of genset failure, most of the electrical installations are not designed to be fed from other generators. Several electrical configurations for diesel generators interconnections have been studied, in order to guarantee the mutual succor between them and therefore improving reliability. Two innovative schemes for emergency generators connection are here proposed for a more reliable electrical design.

Comparison between different electrical configurations of emergency diesel generators for redundancy and reliability improving / TOBIA RODRIGUEZ, MANUEL ALFONSO; Santini, Ezio; Elia, Stefano. - In: PERIODICA POLYTECHNICA. ELECTRICAL ENGINEERING AND COMPUTER SCIENCE. - ISSN 2064-5279. - 62:4(2018), pp. 144-148. [10.3311/PPee.13242]

Comparison between different electrical configurations of emergency diesel generators for redundancy and reliability improving

TOBIA RODRIGUEZ, MANUEL ALFONSO
Membro del Collaboration Group
;
Santini, Ezio
Membro del Collaboration Group
;
Elia, Stefano
Primo
Membro del Collaboration Group
2018

Abstract

The failure of an emergency diesel generator could cause a blackout with economic or human losses, especially if it occurs in a hospital. The authors performed an up to date statistic on diesel generators fails has been investigated in a hundred of hospitals. Although standard maintenance operation has been correctly performed, it has been found a 6 % of failures for the genset per year. MTBF of generators and main components have been investigated and updated values are reported in this paper. Components reliability is proved to be at its maximum technological value, consequently an innovative solution is here proposed. Often neighboring buildings or different electrical systems have separated emergency generators. Nowadays, in case of genset failure, most of the electrical installations are not designed to be fed from other generators. Several electrical configurations for diesel generators interconnections have been studied, in order to guarantee the mutual succor between them and therefore improving reliability. Two innovative schemes for emergency generators connection are here proposed for a more reliable electrical design.
2018
electrical power plants, diesel generators, essential electrical systems, MTBF, reliability
01 Pubblicazione su rivista::01a Articolo in rivista
Comparison between different electrical configurations of emergency diesel generators for redundancy and reliability improving / TOBIA RODRIGUEZ, MANUEL ALFONSO; Santini, Ezio; Elia, Stefano. - In: PERIODICA POLYTECHNICA. ELECTRICAL ENGINEERING AND COMPUTER SCIENCE. - ISSN 2064-5279. - 62:4(2018), pp. 144-148. [10.3311/PPee.13242]
File allegati a questo prodotto
File Dimensione Formato  
Elia_comparison_2018.pdf

accesso aperto

Tipologia: Versione editoriale (versione pubblicata con il layout dell'editore)
Licenza: Creative commons
Dimensione 502.44 kB
Formato Adobe PDF
502.44 kB Adobe PDF

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11573/1211875
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 8
  • ???jsp.display-item.citation.isi??? ND
social impact